Graco E-Flo iQ Operation Manual page 57

Dispense system
Table of Contents

Advertisement

Error
Location Type
CBV_
AMZ
Alarm
CCD_
Driver
Alarm
CCF_
FCM
Alarm
CCG_
Gateway
Alarm
CCH_
Gateway
Alarm
CCN_
Driver
Alarm
CCT_
AMZ
Alarm
CCV_
AMZ
Alarm
DB1_
Pump
Alarm or
DB2_
Deviation
(user
selectable)
333587B
Error
Error Name
Description
Communication
Communication
Error H_
lost between
AMZ DB and
ADM
Duplicate Module
Multiple pumps
P_
using same
pump ID
FCM Comm.
No
Error P_
communication
with the FCM
Fieldbus Comm.
No
Error P_
communication
with the
fieldbus
Fieldbus Comm.
No
Error H_
communication
with the
fieldbus
Control Board P_
Communication
lost between
driver hot and
cold boards
Duplicate Module
Multiple AMZ
H_
MZLP4s using
same module
ID
Duplicate Module
Multiple AMZ
H_
DBs using
same module
ID
Pump Not
Pump has not
Primed P_
been primed
since last
empty drum
Cause
Solution
No AC power to the
Verify AMZ DB is turned on by confirming
AMZ DB
disconnect switch of the heat box is in the
ON position.
AC disconnect
Disconnect AMZ DB from AC power. Check
switch broken
wiring to switch. If wiring is good, replace the
AC disconnect switch of the heat box.
Faulty AMZ DB
Replace AMZ DB control board.
control board
Two or more pumps
Update the pumps displaying the error to the
have the same
latest software available on help.graco.com.
pump ID
The FCM lost
Restore communication.
communication with
the pump
The automation
Restore communication.
gateway lost
communication with
the automation
controller
The automation
Restore communication.
gateway lost
communication with
the heat automation
controller
Software update
If software updates to the hot or cold driver
failure
boards fail before completion, then they will
not be able to communicate. Update
software to the latest available on
help.graco.com.
Cold board
Disconnect pump from AC power. Verify the
disconnected from
cold board is securely fastened on the
hot board
spacers above the hot board.
Faulty driver control
Replace driver control board.
board
Two or more AMZ
Turn dial on AMZ to an non used module ID.
MZLP4s have the
same module ID
Two or more AMZ
Turn dial on AMZ to an non used module ID.
DBs have the same
module ID
Replacing an empty
After replacing an empty drum, the pump
drum with a new
must be primed before returning to operation
one
(if alarm selected). Go to the pump run
screen and push the lower right softkey to
being the priming sequence, then press the
upper right softkey. Set the priming time in
the setup screens. If deviation selected,
prime pump if desired or clear deviation and
return to normal pump operation.
Troubleshooting
57