5.5
Wiring
Basics
The NEA SMART 2.0 communication architecture consists of two
separate BUS systems.
The Zone Bus (ZOBUS) connects the NEA SMART 2.0 Base, the NEA
SMART 2.0 R-Module and the wired room units. The following needs
to be considered:
- 2-wire
- Polarity reversal protected
- Using any topology
- No special requirements for line type
Fig. 5-1
Zone Bus and System Bus
Connection between
Unit 1
Unit 2
Base
Room unit Bus
Room unit Bus
Room unit Bus
Base
R-Module
Base
Base
Base
U-Module
Tab. 5-9 Recommended cable types
Maximum length is 100 m in case I (Y) St Y 2 x 2 x 0,8 mm is used.
Maximum length may differ if other cable types are used.
The System Bus (SYSBUS) connects the NEA SMART 2.0 Bases and the
NEA SMART 2.0 U-Modules. The following rules must be considered:
- Must be installed in series
- Requires shielded twisted pair line.
- Maximum length is 500 m in case I (Y) St Y 2 x 2 x 0,8 mm is used.
Maximum length may differ if other cable types are used.
The use of existing wires is possible, but certain rules need to be
followed.
Communication system
Cable type recommended / alternative
I (Y) St Y 2 x 2 x 0,8 mm / existing 2-wire line
ZOBUS
Zone Bus
I (Y) St Y 2 x 2 x 0,8 mm / existing 2-wire line
ZOBUS
Zone Bus
I (Y) St Y 2 x 2 x 0,8 mm / existing 2-wire line
ZOBUS
Zone Bus
I (Y) St Y 2 x 2 x 0,8 mm
SYSBUS
System Bus
I (Y) St Y 2 x 2 x 0,8 mm
SYSBUS
System Bus
Topology / maxi-
mum lenght
Any / 100 m
Any / 100 m
Any / 100 m
Line / 500 m
Line / 500 m
43