9.2.1

Cooling circuits

To find in App:
Home  More  Settings  Installer  Control Parameters  Cooling  Cooling Circuits
Key
Text in parameter menu Comment
CAn
Min.value supply temp.
cooling mode (normal)
CBn
Flow temp. : safety
distance to dew point
CCn
Element temperature limit
in cooling mode
CDn
Return temperature limit in
cooling mode
CEn
Increase cooling flow
temp. in reduced mode
Tab. 9-4 Parameter cooling circuits
9.3

Mixing circuit control

To find in App:
Home  More  Settings  Installer  Control Parameters  Mixed Circuit Controls
Key
Text in parameter menu Comment
MIXG1
Proportional band-width
heating circuits
MIXG2
Proportional band-width
heating circuits
MIXG3
Integral time mixed circuits Integral time in secs of controller in heating- and coo-
MIXG4
Minimum value control
signal
MIXG5
Maximum value control
signal
MIXG6
Delay time for enabling
PI-Controller
Tab. 9-5 Parameter mixing circuit control
Minimum value of flow temperature in normal mode
(not reduced mode)
The flow temperature always has this safety distan-
ce to the worst (highest) value of the dew point tem-
perature
The temperatue of cooled elements must not be
below this value in cooling mode
The return temperatur must not be below this value in
cooling mode
In reduced mode (energy safe mode) the flow tempe-
rature will be increased by this value.
Proportional band of PI-Controller. Affects the strenght
of the immediate reaction to temperature change. The
wider the band, the weaker the reaction
Proportional band of PI-Controller. Affects the strenght
of the immediate reaction to temperature change. The
wider the band, the weaker the reaction
ling mode. Affects the reaction to permanent deviati-
on to the set point. The longer the time, the slower the
reaction. 0 means OFF
Minimum value of control signal for the actuator of
mixing circuit
Maximum value of control signal for the actuator of
mixing circuit
Delay for enabling the PI-controller after activation of
the heating circuit pump.
Min
Max
Base
value
8
25
16
–5
10
2
15
25
20
10
25
18
0
10
1
Min
Max
Base
value
2
80
20
2
80
10
0
999
60
0
100
0
0
100
100
0
999
15
Unit
° C
K
° C
°C
K
Unit
K
K
sec
%
%
sec