9.5.3

Dehumidifier control

To find in App:
Home  More  Settings  Installer  Device  Dehumidifier
Key
Text in parameter menu Comment
DHAN
Activation dehumidifier in
normal mode
DHRN
Activation dehumidifier in
reduced mode
DE3
Hysteresis relative humi-
dity
DE4
Dewpoint-Limit for the
activation of dehumidifier
DE5
Hysteresis dew point
DE6
Minimum runtime dehu-
midifier
DE7
Blocking time before
restart
DE8
Dehumidifying outside
cooling mode allowed
DE9
Maximum runtime dehu-
midifier
DE10
Dewpoint-Limit for the
activation of dehumidifier
in reduced mode
Tab. 9-9 Parameter dehumidifier control
100
When this value of relative humidity is exceeded, the
dehumidifier is started during the enable time of his
timing program.
When this value of relative humidity is exceeded, the
dehumidifier is started during the enable time of his
timing program.
One-sided hysteresis around the switching threshold
When this dew point value is exceeded the assigned
dehumidifier will be started
One-sided hysteresis around the switching threshold
(switch off point is by this value below DE4)
Minimum demand time for dehumidifier
After end of operation of dehumidifier the next de-
mand signal will be soonest after this delay time.
Dehumidification is also allowed outside of cooling
period (Y/N)
Maximum run time for dehumidifier
When this dew point value is exceeded the assigned
dehumidifier will be started outside the enable time of
his timing program
Min
Max
Base
value
30
90
55
50
90
80
0
20
5
10
25
15
0
2
0,5
0
20
10
0
20
10
false
true
false
30
999
240
10
25
17
Unit
%
%
%
°C
K
min
min
min
min

Advertisement

Table of Contents
loading

Table of Contents