4.2 CONTROLLER PANEL
Fig.1 - HGM6110N/ HGM6110NC/ HGM6110CAN Front Panel Indication
Fig.2 - HGM6120N/ HGM6120NC/ HGM6120CAN Front Panel Indication
Note: Partial indicator states:
Alarm Lamp: slowly blink when warning alarms; fast blink when shutdown alarms; won't illuminate when there is no
alarm.
Status Lamp: won't illuminate when genset stand by; blink 1 time per second in start or stop process and always
illuminate when runs normally; for HGM6100CAN, press start key in auto mode or manual mode, ECU power output and
status lamp always illuminate.