CONTROLLER BACK PANEL

Terminals description as follows,
No.
Function
1
DC Voltage Input B-
2
DC Voltage Input B+
3
Emergency Stop Input
4
Fuel Output
5
Crank Output
6
Remote Start Input
7
Aux. Input
8
Oil Pressure Input
9
Engine Temp. Input
10
Magnetic Pickup
11
Gen Volt Monitoring
Input
12
HGM1790N Genset Controller
HGM1790N GENSET CONTROLLER USER MANUAL
Cable Size
2
1.5mm
Connect to negative of starter battery
Connected to positive of starter battery. If wire length
2
1.5mm
is over 30m, better to double wires in parallel. Max.
20A fuse is recommended.
B+ voltage input is active, and connected to
2
1.0mm
emergency stop normal closed button.
2
1.0mm
B+ is supplied by No.3 point, rated 1A.
2
1.0mm
B+ is supplied by No.3 point, rated 1A.
2
1.0mm
Ground connected is active (B-)
Ground connected is active (B-) if it is configured as
switch input value.
2
1.0mm
Connect to low fuel level switch value or fuel level
resistor type sensor.
Connect to low oil pressure switch value or resistor
2
1.0mm
type sensor.
Connect to high water/cylinder temp. switch value or
2
1.0mm
temperature resistor type sensor.
Connect to speed sensor, and shielded wire is
2
0.5mm
recommended.
The other end of speed sensor is connected to B-.
2
1.0mm
Connect to generator voltage output port.
2
(2A fuse is recommended)