3 SPECIFICATION

Items
Working Voltage
Power Consumption
AC System
3P4W
3P3W
1P2W
2P3W
AC Alternator Frequency
Rotate speed sensor Voltage
Rotate speed sensor Frequency
Start Relay Output
Fuel Relay Output
Auxiliary Relay Output 1
Auxiliary Relay Output 2
Auxiliary Relay Output 3
Auxiliary Relay Output 4
Overall Dimensions
Panel Cutout
C.T. Secondary Current
Working Condition
Storage Condition
Protection Level
Insulation Intensity
Weight
HGM6100N Genset Controller
HGM6100N Series Genset Controller User Manual
Table 2 – Technical Parameters
DC8.0V to DC35.0V, continuous
<3W(Standby mode: ≤2W)
AC15V - AC360 V (ph-N)
AC30V - AC620 V (ph-ph)
AC15V - AC360 V (ph-N)
AC15V - AC360 V (ph-N)
50Hz/60Hz
1.0V to 24V (RMS)
10,000 Hz (max.)
16 A DC28V at supply voltage
16 A DC28V at supply voltage
7 A DC28V at supply voltage
7 A AC250V volt-free output
16 A AC250V volt-free output
16 A AC250V volt-free output
209mm x 166mm x 45mm
186mm x 141mm
5A (rated)
Temperature: (-25~70)º C; Relative Humidity: (20~93)%RH
Temperature: (-30~+80)º C
IP65: when water-proof gasket installed between control panel and
enclosure.
Apply AC2.2kV voltage between high voltage terminal and low
voltage terminal. The leakage current is not more than 3mA within
1min.
0.56kg