Emergency Start - Smartgen HGM6100N Series User Manual

Genset controller
Hide thumbs Also See for HGM6100N Series:
Table of Contents

Advertisement

high speed running. If there is high temperature, low oil pressure, over speed and abnormal voltage
during genset running, controller can protect genset to stop (detail procedures please refer to
No.4~9 of Auto start operation). Under Manual Mode, switch won't transfer automatically, it is
necessary to press
2)
HGM6110,
Manual
press
to start genset, it can automatically detect crank disconnect and accelerate to high
speed running. If there is high temperature, low oil pressure, over speed and abnormal voltage
during running, controller can protect genset to stop quickly (detail procedures please refer to
No.4~9 of Auto start operation). After genset runs well in high speed, press
3)
Manual stop, pressing
No.3~7 of Auto stop operation).

4.5 EMERGENCY START

In manual mode, pressing
whether the controller has started successfully according to disconnect conditions and the disconnection of
starter needs to control by operators. When operators observed the genset has started successfully, loose
the keys and the controller enter safety delay with start stops to output.
5 PROTECTION
5.1 WARNINGS
When controller detects the warning signal, the genset only alarm and not stop. The alarms are
displayed in LCD.
No.
Items
1
Loss Of Speed Signal
2
Genset Over Current
3
Fail To Stop
4
Low Fuel Level
5
Failed To Charge
HGM6100N Genset Controller
to transfer load.
Mode is active when pressing
can shut down the running genset (detail procedures please refer to
and
Table 4 – Controller Warning Alarms
When the speed of genset is 0 and speed loss delay is 0, controller will
send warning alarm signal and it will be displayed in LCD.
When the current of genset is higher than threshold and setting over
current delay is 0, controller will send warning alarm signal and it will be
displayed in LCD.
When genset cannot stop after the ―stop delay‖ is over, controller will send
warning alarm signal and it will be displayed in LCD.
When the fuel level of genset is lower than threshold or low fuel level
warning is active, controller will send warning alarm signal and it will be
displayed in LCD.
During genset normal running process, when the voltage difference
2019-03-28
HGM6100N Series Genset Controller User Manual
, and its indicator is illuminating. Then
can compel genset to start. The controller won't judge
Description
Version 1.5
and gens take load.
Page 11 of 42