6 CONNECTIONS
Compared with HGM6120, HGM6110 doesn't have 3-phase input terminal of mains voltage. The
back panel of HGM6120 is as below.
No.
Function
1
DC input B-
2
DC input B+
3
Emergency Stop
4
Fuel Relay Output
5
Start Relay Output
6
Aux. Relay Output 1
7
8
Aux. Relay Output 2
9
10
Aux. Relay Output 3
11
12
Aux. Relay Output 4
13
HGM6100N Genset Controller
Fig.3 – Controller Rare Panel Drawing
Table 6 – Terminal Connection Description
Cable Size
2
2.5mm
Connected to negative of starter battery
Connected to positive of starter battery. If wire length is
2
2.5mm
over 30m, better to double wires in parallel. Max. 20A
fuse is recommended.
2
2.5mm
Connected to B+ via emergency stop button.
2
1.5mm
B+ is supplied by 3 points, rated 16A
B+ is supplied by 3 points, rated 16A Connect to starter
2
1.5mm
coil
2
1.5mm
B+ is supplied by 2 points, rated 7A
Normal close output, 7 A rated.
2
1.5mm
Relay common port
Normal open output, 7 A rated.
2
2.5mm
Relay normal open volt-free contact
output
2
16 A rated
2.5mm
2019-03-28
HGM6100N Series Genset Controller User Manual
Description
Version 1.5
Reference Table 8
Page 15 of 42