General guidelines for commissioning
4189340703 UK
Analogue controller or EIC, J1939
As an initial setting before the first start up, the K
to a value giving a slow regulation. This means that K
set to a high value.

4.1.7 Voltage controller settings

The voltage controller settings are adjusted in the regulation part of the control setup menu.
The screendump above illustrates the controller settings of the voltage and reactive power controller. As an
initial setting before the first start up, the K
value giving a slow regulation.
Analogue controller or J1939
As an initial setting before the first start up, the K
a value giving a slow regulation. This means that K
set to a high value.
DEIF A/S
, Ti and Td of the frequency and power controllers are set
p
and Td should be set to a low value, and Ti should be
p
of the voltage and reactive power controllers are set to a low
p
, Ti and Td of the frequency and power controllers are set to
p
and Td should be set to a low value, and Ti should be
p
Settings
Page 12 of 25