To Connect The Remote Outdoor Sensor; To Connect The Shut-Off Valve - Daikin Altherma 3 GEO EGSAH06UD Series Installation Manual

Table of Contents

Advertisement

Detail C5: Option kit EKGSPOWCAB
Install the option kit EKGSPOWCAB (= power cable for split
power supply). For installation instructions, see the installation
manual of the option kit.
Z15C
N=1
EKGSPOWCAB
1
3
I
I
F2B
2
4
Q2DI
L
N
1N~, 50 Hz, 230 V AC
F2B
Overcurrent fuse (field supply). Recommended fuse:
2‑pole, 16 A fuse, C curve.
Q2DI
Earth leakage circuit breaker (field supply)
Configuration power supply
[9.3] Backup heater
[9.8] Benefit kWh power supply
6.5
To connect the remote outdoor
sensor
The remote outdoor sensor (delivered as accessory) measures the
outdoor ambient temperature.
INFORMATION
If the desired leaving water temperature is weather
dependent, the full time outdoor temperature measurement
is important.
Remote outdoor sensor + cable (40 m) delivered as accessory
[9.B.2] Ext. amb. sensor offset (= overview field setting
[2‑0B])
[9.B.3] Averaging time (= overview field setting [1‑0A])
1 Connect the external temperature sensor cable to the indoor
unit.
a
b
c
a
Factory-mounted cable
b
Splicing connectors (field supply)
EGSAH/X06+10UD
Daikin Altherma 3 GEO
4P598591-1C – 2023.02
X22YB
X22Y
1
Z2F/1
2
Z2F/2
3
Z2F/3
d
c
Remote outdoor sensor cable (40 m)(delivered as
accessory)
d
Remote outdoor sensor (delivered as accessory)
2 Fix the cable with cable ties to the cable tie mountings.
3 Install the remote outdoor sensor outside as described in the
installation manual of the sensor (delivered as accessory).
6.6

To connect the shut-off valve

INFORMATION
Shut-off valve usage example. In case of one LWT zone,
and a combination of underfloor heating and heat pump
convectors, install a shut-off valve before the underfloor
heating to prevent condensation on the floor during cooling
operation.
Wires: 2×0.75 mm²
Maximum running current: 100 mA
230 V AC supplied by PCB
[2.D] Shut off valve
1 Open the following (see
"4.2.1 To open the indoor
1 Top panel
2 User interface panel
3 Installer switch box cover
2 Connect the valve control cable to the appropriate terminals as
shown in the illustration below.
NOTICE
Wiring is different for a NC (normally closed) valve and a
NO (normally open) valve.
M2S
NO
X2M
3 Fix the cable with cable ties to the cable tie mountings.
6 Electrical installation
unit" [ 4  6]):
1
NC
OR
X2M
Installation manual
3
2
19