2.6

I-Demand Function

Purpose
Set a limitation towards the power consumption from the system.(e.g. budget control, limit
power consumption during peak moments,..)
Setting
3 different demand setting can be selected by using terminal X801M:
 Demand 1  Close contact between COM and contact 1
 Demand 2  Close contact between COM and contact 2
 Demand 3  Close contact between COM and contact 3
Demand 1
Power consumption limitation in function of setting on DS1:
Demand 2
Power consumption limitation set to 40%.
Demand 3
Forced thermostat OFF.
Field Setting
Power supply connector
(on outdoor PCB X77A)
X801M
COM
3
2
1
LNOP
DS1 Setting
1
OFF
ON
OFF
ON
Field Setting from Remote Controller
DS1
ON
OFF
1 2 3 4
X800M
3
2
1
LNOP COM
2
OFF
OFF
ON
ON
Transmission connector
(on outdoor PCB X6A)
X801M
Output on X801M =
12VDC, 12mA
Maximum wire length =
100 meter
Maximum Power
Consumption
60%
70%
80%
100%