UPS2000-A-(6 kVA-10 kVA)-RTL
User Manual

9.6 Battery Electrical Specifications

Issue 07 (2020-01-10)
Item
Output power factor
Rated output voltage
Output voltage precision
Total harmonic distortion of the
output voltage waveform (THDv)
Crest factor
Overload capacity
Dynamic voltage transient
Average frequency tracking rate
Item
Rated battery voltage
Number of batteries
Leakage current
Power backup time
Copyright © Huawei Technologies Co., Ltd.
6 kVA/10 kVA
0.9 (When the power factor ranges from 0.5 to 1, the
UPS2000-A with inductive load is not derated. When
the power factor ranges from 0.5 to 1, the UPS2000-A
with 80%–100% capacitive load is linearly derated.)
220 V AC/230 V AC/240 V AC (selected by setting a
voltage level on the LCD.)
± 1%
≤ 5% (configured with a residual current device
(RCD) with a 0.7 power factor, and specified in
the IEC62040 standards of THDv.)
≤ 2% (resistive load. Each harmonic meets the
limit specified by the IEC62040.)
A maximum of 3:1
Normal mode, 105%–125% load: The UPS
transfers to bypass mode in 5 minutes if the bypass
is normal or disconnects the output if the bypass is
abnormal.
Normal mode, 125%–150% load: The UPS
transfers to bypass mode in 1 minute if the bypass
is normal or disconnects the output if the bypass is
abnormal.
Normal mode, ≥ 150% load: The UPS transfers to
bypass mode in 0.2 second if the bypass is normal
or disconnects the output if the bypass is
abnormal.
± 5%
0.5–2 Hz/s for a single UPS
6 kVA/10 kVA
192–240 V DC
12 V lead-acid batteries; a long backup time model
connects to external battery packs with 16–20
batteries configured.
≤ 500 µA
Determined by the battery capacity.
For the power backup time of the battery pack
for the 6 kVA UPS, see
9 Technical Specifications
Table
9-1.