UPS2000-A-(6 kVA-10 kVA)-RTL
User Manual
Step 10 After checking that the system is running properly, turn on the load switch to start the load.
----End

5.2.2 Shutting Down the UPS

Shutting Down the Inverter to Transfer the UPS to Bypass Mode
To shut down the inverter, perform any of the following operations:
Issue 07 (2020-01-10)
On the default screen, hold down
when you hear a beep sound. If the UPS starts successfully, it enters normal mode, as
shown in
Figure
5-15.
Figure 5-15 Battery mode
On the standby screen, hold down
CTR menu. If the UPS starts successfully, it enters normal mode, as shown in
16.
Figure 5-16 Battery mode
To prevent triggering overload protection, start the loads with higher power and then loads with lower
power.
On the default screen, hold down ESC for more than 5 seconds. Release the button when
you hear a beep sound. The inverter shuts down, and the UPS transfers to bypass mode.