A Technical Specifications; Environmental Specifications; Electrical Specifications - Huawei Telecom Power TP48200A-HT19C3 User Manual

Table of Contents

Advertisement

TP48200A-HT19C3 and TP48200A-HT19C4 Telecom
Power
User Manual
A.1 Environmental Specifications
Table A-1 Environmental specifications
Item
Operating temperature
Transportation temperature
Storage temperature
Operating humidity
Storage humidity
Altitude
Noise level
A.2 Electrical Specifications
Table A-2 Electrical specifications
Item
Specifications
AC input
AC input system
AC input voltage
Input frequency
Issue 03 (2019-11-15)
A
Technical Specifications
Specifications
-10° C to +45° C
-40° C to +70° C
-40° C to +70° C
5%-95% RH
5%-95% RH
0-4000 m
When the altitude ranges from 2000 m to 4000 m, the operating
temperature decreases by 1° C for each additional 200 m.
Complies with GR487. Acoustic pressure level: <65dBA@1.5 m
Copyright © Huawei Technologies Co., Ltd.

A Technical Specifications

TP48200A-HT19C3: 220/380 V AC
three-phase, four-wire and compatible
with 220 V AC single-phase
TP48200A-HT19C4: 110 V AC
dual-live wire
85 V AC-300 V AC
Frequency range: 45-66 Hz; nominal
frequency: 50 Hz or 60 Hz
82

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Telecom Power TP48200A-HT19C3 and is the answer not in the manual?

Questions and answers

This manual is also suitable for:

Telecom power tp48200a-ht19c4Tp48200a-ht19c3Tp48200a-ht19c4

Table of Contents