UPS2000-A-(6 kVA-10 kVA)-RTL
User Manual
Alarm
Alarm
Name
ID
Internal
2A
fault
Internal
2A
fault
Internal
2A
fault
Internal
2A
fault
Internal
2A
fault
Internal
2A
fault
Issue 07 (2020-01-10)
Alarm
Alarm
Alarm
Cause
level
Clear Mode
ID
13
Critica
Power-off
l
clear
14
Critica
Automatic
l
clear
17
Critica
Manual
l
clear/Power-
off clear
18
Critica
Manual
l
clear/Power-
off clear
1B
Critica
Power-off
l
clear
1C
Critica
Power-off
l
clear
Copyright © Huawei Technologies Co., Ltd.
Impact on the
System
The UPS shuts
down or transfers to
another working
mode.
The UPS shuts
down or transfers to
working mode; the
charger stops
working.
The UPS shuts
down.
N/A
The inverter shuts
down. The UPS
transfers to bypass
mode or has no
output.
The UPS shuts
down or transfers to
another working
A Alarm Handling
Repair Proposal
fault and restart the
UPS.
Possible cause: The
hardware is damaged.
Measure: Contact
Huawei technical
support.
Possible cause: The
ambient temperature
exceeds 40º C.
Measure: Lower the
ambient temperature.
Possible cause: Air
channels are blocked.
Measure: Keep the
air intake and exhaust
vents of the UPS
unblocked.
Possible cause: The
fan is abnormal.
Measure: Clean up
the foreign matter
around the fan. If the
alarm persists,
contact Huawei
technical support.
Possible cause: The M4
or CPLD chip is faulty.
Measure: Contact
Huawei technical
support.
Possible cause: The
EEPROM chip is faulty.
Measure: Contact
Huawei technical
support.
Possible cause: The
inverter is faulty.
Measure: Contact
Huawei technical
support.
Possible cause: The
inversion relay is faulty.
92