UPS2000-A-(6 kVA-10 kVA)-RTL
User Manual
Alarm
Alarm
Name
ID
Remaining
22
cap.
warning
Battery
1B
overcurrent
Battery
1D
maintenanc
e required
Issue 07 (2020-01-10)
Alarm
Alarm
Alarm
Cause
level
Clear Mode
ID
1
Minor
Automatic
clear
1
Minor
Automatic
clear
1
Minor
Manual clear
Copyright © Huawei Technologies Co., Ltd.
Impact on the
System
If no action is taken,
continued discharge
will result in system
shutdown due to
EOD.
An alarm is
generated, and the
battery lifespan is
affected.
The battery backup
time is affected.
A Alarm Handling
Repair Proposal
Possible cause: The
charger is abnormal.
Measure: Check that
the charger voltage is
normal immediately
after the batteries are
disconnected.
Possible cause: The
battery discharge
lasts too long.
Measure: Check the
mains, and charge
batteries in a timely
manner.
Possible cause: The
mains input is
abnormal.
Measure: Check the
mains, and charge
batteries in a timely
manner.
Possible cause: The
number of batteries
or battery capacity is
incorrectly set.
Measure: Check the
configured battery
capacity.
Possible cause: The
charger is abnormal.
Measure: Contact
Huawei technical
support.
Possible cause: The
battery capacity is
incorrectly
configured.
Measure: Check that
the configured battery
capacity is consistent
with the actual
battery capacity.
Possible cause: The
battery circuit cannot
discharge currents.
Measure: Check the
89