UPS2000-A-(6 kVA-10 kVA)-RTL
User Manual
9.4 Bypass Input Electrical Specifications
9.5 Output Electrical Specifications
Issue 07 (2020-01-10)
Item
Rated input voltage
Input voltage
Input frequency
Input power factor (100% load)
No-load loss
Startup voltage
Diesel
Item
Bypass voltage range
Bypass frequency range
Bypass overload capability
Input mode
Item
Rated capacity
Copyright © Huawei Technologies Co., Ltd.
6 kVA/10 kVA
220 V AC, 230 V AC, or 240 V AC
80–280 V AC (When the voltage is 80–176 V AC, the
load power is linearly derated to 40%–100%.)
45–55 Hz/55–65 Hz
> 0.99
6 kVA: < 54 W
10 kVA: < 90 W
120–280 V AC
Minimum: 1.5 times the UPS rated capacity
6 kVA/10 kVA
Upper threshold: 10%, 15%, 20%, or 25% at 220 V
AC
Upper threshold: 10%, 15%, or 20% at 230 V AC
Upper threshold: 10%, or 15% at 240 V AC
Lower threshold: 10%, 20%, 30%, 40%, 50%, or 60%
Maximum ± 5 Hz
Load < 125%: The UPS continuously works. The
input circuit breaker may trip in advance.
125% ≤ load < 150%: The UPS stops power output
after 1 minute. The input circuit breaker may trip in
advance.
Load ≥ 150%: The UPS stops power output after 200
ms. The input circuit breaker may trip in advance
(load is calculated based on the bypass currents).
Single mains
6 kVA/10 kVA
6 kVA/10 kVA
9 Technical Specifications
79