UPS2000-A-(6 kVA-10 kVA)-RTL
User Manual
Step 10 After checking that the system is running properly, turn on the load switch to start the load.
----End
Starting the UPS in Battery Mode
Step 1 Close the external battery circuit breakers (if any), or connect battery cables.
Step 2 Press
Step 3 After the LCD screen lights up for 1s, the initialization screen is displayed. After the progress
bar is complete, the default screen is displayed, as shown in
Figure 5-9 Power-on and default screen
Step 4 Set the voltage level based on the actual output voltage. The voltage level can be set to 220 V
(default), 230 V, or 240 V.
Figure 5-10 Setting the voltage level
Step 5 Set the system output frequency level based on the rated frequency. The values include 50 Hz
(default), 60 Hz, and Automatic.
Issue 07 (2020-01-10)
To prevent triggering overload protection, start the loads with higher power and then loads with lower
power.