UPS2000-A-(6 kVA-10 kVA)-RTL
User Manual
Alarm
Alarm
Name
ID
Internal
2A
fault
Internal
2A
fault
Internal
2A
fault
Internal
2A
fault
Issue 07 (2020-01-10)
Alarm
Alarm
Alarm
Cause
level
Clear Mode
ID
0E
Critica
Manual
l
clear/Power-
off clear
0F
Critica
Manual
l
clear/Power-
off clear
11
Critica
Manual
l
clear/Power-
off clear
12
Critica
Manual
l
clear/Power-
off clear
Copyright © Huawei Technologies Co., Ltd.
Impact on the
System
The UPS shuts
down or transfers to
another working
mode.
The UPS cannot
start.
The UPS shuts
down or transfers to
another working
mode.
The UPS shuts
down or transfers to
another working
mode.
A Alarm Handling
Repair Proposal
Measure: Reconnect the
self-load cables.
Possible cause: The soft-
start resistor is damaged.
Measure: Contact
Huawei technical
support.
Possible cause: The
rectifier circuits are
damaged.
Measure: Contact
Huawei technical
support.
Possible cause: The
mains has
experienced a
transient high
voltage.
Measure: Rectify the
fault and restart the
UPS.
Possible cause: The
output supplies power
to special loads such
as the inductive and
rectification loads.
Measure: Check that
the load types are
supported by the
UPS.
Possible cause: The
hardware is damaged.
Measure: Contact
Huawei technical
support.
Possible cause: The
hardware is damaged.
Measure: Contact
Huawei technical
support.
Possible cause: An
overload occurred
when the input
voltage was low.
Measure: Rectify the
91