UPS2000-A-(6 kVA-10 kVA)-RTL
User Manual
Name
Screen
Discharge
time
protection
setting
ECO
mode
enabling
Issue 07 (2020-01-10)
Function
Set the maximum
discharge time.
When the
discharge time
reaches the value,
the system powers
off. If you set the
value to 0, the
discharge time is
not limited.
Indicates whether
to allow a single
UPS to work in
ECO mode.
Copyright © Huawei Technologies Co., Ltd.
Value
Preset
Range
Value
0–24 hours
16 hours
DIS
DIS
(disabled)
and ENA
(enabled)
4 Control Panel
Remarks
The value is
configurable
in non-battery
mode or non-
battery ECO
mode.
The value is
configurable
only after the
inverter shuts
down.
54