UPS5000-H-400 kVA & 800 kVA-NTN Quick Guide (Singapore 1-NET, 100 kVA Power Modules)
01
Installing Cabinets
1. Before installation, read the user manual carefully to get familiar with product information and safety precautions.
2. Use insulated tools when installing the equipment.
3. Only engineers certified by Huawei or its agent are allowed to install, commission, and maintain the UPS. Otherwise, personal injury or equipment damage
may occur, and the resulting UPS faults are beyond the warranty scope of Huawei.
4. This document describes the installation procedure for a single UPS. For details about how to install a parallel system, contact Huawei technical support.
Installing Cabinets (400 kVA)
Space Planning
Unpacking
Inductor
UPS
cabinet
cabinet
Inductor
cabinet
Cabinet Description
Rectifiers
Main switch QF of
the inductor cabinet
Fan power switch QS
Fans
风扇
安装流程
UPS
cabinet
Power distribution
cover
Control module
PSU for fans
Bypass modules
Power modules
功率模块
Model
Weight
UPS cabinet: < 800 kg
UPS5000-H-400K-NTN
Inductor cabinet: < 550 kg
UPS cabinet: < 1300 kg
UPS5000-H-800K-NTN
Inductor cabinet: < 550 kg
Securing the
Cabinet
1
Issue: 01
Date: 2021-07-14
Dimensions (H x W x D)
UPS cabinet: 2000 mm x 800 mm x 1000 mm
Inductor cabinet: 2000 mm x 400 mm x 1000 mm
UPS cabinet: 2000 mm x 1600 mm x 1000 mm
Inductor cabinet: 2000 mm x 400 mm x 1000 mm
M12 bolt
Spring washer
Flat washer
Concrete floor
Expansion sleeve
Expansion nut

Advertisement

loading

Summary of Contents for Huawei UPS5000-H-400K-NTN

  • Page 1 UPS cabinet: < 1300 kg UPS cabinet: 2000 mm x 1600 mm x 1000 mm 3. Only engineers certified by Huawei or its agent are allowed to install, commission, and maintain the UPS. Otherwise, personal injury or equipment damage UPS5000-H-800K-NTN Inductor cabinet: <...
  • Page 2 UPS5000-H-400 kVA & 800 kVA-NTN Quick Guide (Singapore 1-NET, 100 kVA Power Modules) 安装流程 Installing Cabinets (800 kVA) Unpacking Securing the Cabinet Space planning M12 bolt Spring washer Flat washer cabinet Inductor Concrete floor Expansion sleeve cabinet Expansion nut cabinet Inductor cabinet Cabinet Description...
  • Page 3 UPS5000-H-400 kVA & 800 kVA-NTN Quick Guide (Singapore 1-NET, 100 kVA Power Modules) Installing Rectifiers and Cables Equipotential ground point Installing Rectifiers and Cables(400 kVA) Signal cable route Power cable hole outside the cabinets Signal cable hole Signal cable routing from the inductor cabinet to the UPS cabinet Single power source...
  • Page 4 UPS5000-H-400 kVA & 800 kVA-NTN Quick Guide (Singapore 1-NET, 100 kVA Power Modules) Installing Rectifiers and Cables (800 kVA) Signal cable hole Signal cable route Power cable hole Equipotential ground point Signal cable routing from the inductor cabinet to the UPS cabinet Single power source •...
  • Page 5: Power-On Commissioning

    WebUI passwords after displayed, indicating whether to start the UPS. operator (common user) 000001 Changeme the first login. Tap OK. You can also log in to Huawei technical support website: https://support.huawei.com/enterprise https://support.huawei.com Copyright © Huawei Technologies Co., Ltd. 2021. All rights reserved.