UPS2000-A-(6 kVA-10 kVA)-RTL
User Manual
Figure 5-2 Setting the voltage level
Step 5 Set the system output frequency level based on the rated frequency. The values include 50 Hz
(default), 60 Hz, and Automatic.
Figure 5-3 Setting the output frequency level
Step 6 Set the number of batteries. The default value is 16 for the 6 kVA/10 kVA UPS with long
backup time. The value range is 16 to 20. Set the parameter to the actual number of batteries.
Figure 5-4 Setting the number of batteries
Step 7 Set the battery capacity to the total capacity of all battery strings. The default values for the 6
kVA UPS with long backup time and 10 kVA UPS with long backup time is 40 Ah and 65 Ah
respectively. The value range is 7 Ah to 999 Ah. Set the parameter to the actual battery
capacity.
Figure 5-5 Setting the battery capacity
Issue 07 (2020-01-10)