UPS2000-A-(6 kVA-10 kVA)-RTL
User Manual
Figure 3-4 Cable routes for a rack-mounted UPS
3.2.3 Connecting Cables
Prerequisites
Procedure
Step 1 Turn off the AC input circuit breaker on the rear of the UPS, external output circuit breaker (if
any), and battery circuit breaker.
Step 2 Remove the cover of the AC input, output, and battery wiring terminals from the UPS.
Issue 07 (2020-01-10)
(1) AC output
(2) AC input
power cable
power cable
Ensure that the L and N wires of UPS AC input and output power cables are connected
correctly. Ensure that battery terminals are connected correctly.
Before connecting cables, ensure that the input circuit breaker, external output circuit
breaker (if any), and battery circuit breaker are OFF to avoid operations with power on.
Copyright © Huawei Technologies Co., Ltd.
(3) Cable between the UPS
and the battery pack
3 Installation
(4) Cable between the
battery packs
31