Mains Input Electrical Specifications; Bypass Input Electrical Specifications - Huawei UPS5000-E-12 User Manual

Table of Contents

Advertisement

UPS5000-E-(40 kVA-320 kVA)
User Manual

8.4 Mains Input Electrical Specifications

Item
Input
system
Rated input
voltage
Input
voltage
Input
frequency
Input PF
THDi

8.5 Bypass Input Electrical Specifications

Item
Input
system
Rated
input
voltage
Input
frequen
cy
Bypass
synchro
nization
tracking
frequen
cy
Issue 10 (2015-09-15)
UPS5000-E-120K-F12
0
Three-phase, five-wire
380 V AC, 400 V AC, or 415 V AC (line voltage)
138–485 V AC (line voltage)
The UPS power is not derated at 305–485 V AC and is linearly derated at
305–138 V AC.
40–70 Hz
0.99
< 3% (full linear load); < 5% (full non-linear load)
UPS5000-E-120K-F12
0
Three-phase, five-wire
380 V AC, 400 V AC, or 415 V AC (line voltage)
50 Hz or 60 Hz (tolerance ± 6 Hz)
50 Hz or 60 Hz (tolerance ± 6 Hz)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
UPS5000-E-2
UPS5000-E-3
00K-F200
20K-F320
UPS5000-E-20
UPS5000-E-32
0K-F200
0K-F320
8 Technical Specifications
UPS5000-E-3
20K-F320T
UPS5000-E-32
0K-F320T
207