Huawei UPS2000-A-RTL Series User Manual page 100

Table of Contents

Advertisement

UPS2000-A-(6 kVA-10 kVA)-RTL
User Manual
Alarm
Alarm
Name
ID
Internal
2A
fault
Internal
2A
fault
Internal
2A
fault
Internal
2A
fault
Issue 07 (2020-01-10)
Alarm
Alarm
Alarm
Cause
level
Clear Mode
ID
1D
Critica
Power-off
l
clear
1E
Critica
Power-off
l
clear
1F
Critica
Automatic
l
clear
20
Critica
Automatic
l
clear
Copyright © Huawei Technologies Co., Ltd.
Impact on the
System
mode.
The UPS shuts
down or transfers to
another working
mode.
The UPS shuts
down or transfers to
another working
mode.
The UPS shuts
down or transfers to
another working
mode.
The UPS shuts
down or transfers to
another working
mode.
A Alarm Handling
Repair Proposal
Measure: Contact
Huawei technical
support.
Possible cause: The
inversion relay is faulty.
Measure: Contact
Huawei technical
support.
Possible cause: The
inverter output is short-
circuited.
Measure: Resolve the
short-circuit issue (if
any) for the output
terminal, clear the alarm,
and restart the UPS. If
the alarm persists,
contact Huawei technical
support.
Possible cause: The
mains has
experienced a
transient high
voltage.
Measure: Handle the
high voltage and
restart the UPS.
Possible cause: The
output supplies power
to special loads such
as the inductive and
rectification loads.
Measure: Check that
the load types are
supported by the
UPS.
Possible cause: The
hardware is damaged.
Measure: Contact
Huawei technical
support.
Possible cause: The
ambient temperature
exceeds 40º C.
Measure: Lower the
93

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ups2000-a-6 kva-rtlUps2000-a-10 kva-rtl