Huawei UPS2000-A-RTL Series User Manual page 97

Table of Contents

Advertisement

UPS2000-A-(6 kVA-10 kVA)-RTL
User Manual
Alarm
Alarm
Name
ID
Internal
1E
overtemper
ature
Internal
2A
fault
Internal
2A
fault
Internal
2A
fault
Issue 07 (2020-01-10)
Alarm
Alarm
Alarm
Cause
level
Clear Mode
ID
1
Minor
Automatic
clear
2
Critica
Manual
l
clear/Power-
off clear
3
Minor
Automatic
clear
9
Critica
Automatic
l
clear
Copyright © Huawei Technologies Co., Ltd.
Impact on the
System
The power supply is
not affected.
The UPS shuts
down.
The power supply is
not affected.
The inverter is shut
down.
A Alarm Handling
Repair Proposal
battery cable
connection and the
status of each battery.
Possible cause: The
battery capacity is
lower than normal.
Measure: Replace
battery strings. If the
alarm persists,
manually clear the
alarm.
Possible cause: The
ambient temperature
exceeds 40º C.
Measure: Lower the
ambient temperature.
Possible cause: Air
channels are blocked.
Measure: Keep the
air intake and exhaust
vents of the UPS
unblocked.
Possible cause: The
fan is abnormal.
Measure: Clean up
the foreign matter
around the fan. If the
alarm persists,
contact Huawei
technical support.
Possible cause: The
battery relay or soft-start
resistor is damaged.
Measure: Contact
Huawei technical
support.
Possible cause: The NTC
is not connected or is
damaged.
Measure: Contact
Huawei technical
support.
Possible cause: The self-
load cable connection is
incorrect.
90

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ups2000-a-6 kva-rtlUps2000-a-10 kva-rtl