Huawei UPS2000-A-RTL Series User Manual page 57

Table of Contents

Advertisement

UPS2000-A-(6 kVA-10 kVA)-RTL
User Manual
Name
Screen
Output
frequency
system
Upper
voltage
threshold
Issue 07 (2020-01-10)
Function
Set the system
output frequency
level. If the value
is Automatic, the
power-on bypass
frequency ranges
from 45 Hz to 55
Hz, and the system
output frequency is
50 Hz; if the
power-on bypass
frequency ranges
from 55 Hz to 65
Hz (excluding 55
Hz), the system
output frequency is
60 Hz.
Upper threshold
for the bypass
voltage. When the
difference between
the bypass voltage
and the rated
output voltage
exceeds this value,
the system
determines that the
bypass voltage is
abnormal and that
the bypass is
unavailable. This
parameter is
associated with the
system voltage
level.
Copyright © Huawei Technologies Co., Ltd.
Value
Preset
Range
Value
50 Hz, 60
50 Hz
Hz, and
AUT
(automatic)
If the
15%
voltage
system is
220 V,
the
values
include
10%,
15%,
20%,
and
25%.
If the
voltage
system is
230 V,
the
values
include
10%,
15%,
and
20%.
If the
voltage
system is
240 V,
the
4 Control Panel
Remarks
The value is
configurable
only after the
inverter shuts
down.
The value is
configurable
only after the
inverter shuts
down.
50

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ups2000-a-6 kva-rtlUps2000-a-10 kva-rtl