2. Commissioning

2.2.5 Addressing possibilities of PLC family

PLEASE NOTE
I/O rack no.
Depending on the controller used, the following I/O rack
numbers are possible. Set this address on the field bus
node.
2-8
With a baud rate of 115.2 kBaud all
unused chassis must be set to OFF via SD2.
The LED display for "Chassis" lights up
red (= inactive) on the SD or SD2 adapter.
Data transmission functions correctly.
With PLC controllers you can physically
connect maximum 32 modules via one channel
to the RIO network.
A CP system configured as a half rack,
must always lie within a logical rack.
A-B PLC family
PLC-2
PLC-3
PLC-5/250
PLC-5/15
PLC-5/25
PLC-5/30
PLC-5/40
PLC-5/60
Possible I/O rack no.
2; ...; 7
1; ...; 30
1; ...; 17
01; ...; 03
01; ...; 07
01; ...; 07
01; ...; 17
01; ...; 27
CP FB8 9809a