Table 2-16 Alarms Tab Configuration Parameters - Honeywell UMC800 Reference Manual

Control builder function block
Hide thumbs Also See for UMC800:
Table of Contents

Advertisement

Function Blocks
2.15 CARB Function Block,
Configuration Parameters, continued
ALARMS TAB, continued
Properties Group
Parameter
Alarm 1
Setpoint 1
Setpoint 2
Alarm 2
Setpoint 1
Setpoint 2
Alarm
Hysteresis
Hysteresis
56
continued

Table 2-16 Alarms Tab Configuration Parameters

Index#
17
Alarm 1 Setpoint 1 Value -
this is the value at which you
want the alarm type chosen
below to activate
N/A
Alarm 1 Setpoint 1 Type -
Type
select what you want Alarm 1
Setpoint 1 to represent.
18
Alarm 1 Setpoint 2 Value
N/A
Alarm 1 Setpoint 2 Type
Type
19
Alarm 2 Setpoint 1 Value
N/A
Alarm 2 Setpoint 1 Type
Type
20
Alarm 2 Setpoint 2 Value
Type
N/A
Alarm 2 Setpoint 2 Type
25
Alarm Hysteresis in %
Function Block Reference Guide
Parameter Description
Value or Selection
-99999 to 99999 in
Engineering Units
Selections:
NO ALARM
PV_HIGH
PV_LOW
DEV_HIGH
DEV_LOW
SP_HIGH
SP_LOW
OUT_HIGH
OUT_LOW
Same as Alarm 1
Setpoint 1
Same as Alarm 1
Setpoint 1
Same as Alarm 1
Setpoint 1
Same as Alarm 1
Setpoint 1
Same as Alarm 1
Setpoint 1
Same as Alarm 1
Setpoint 1
0 to 5%