Festo CPX Series Manual page 68

Bus node fieldbus protocol cc-link
Hide thumbs Also See for CPX Series:
Table of Contents

Advertisement

5
Function module F23
Analogue I/O modules (≤ 12 AI / AO) with system diagnostics
– 2 to 4 stations:
2 : ≤ 4 AI / AO
3 : ≤ 8 AI / AO
4 : ≤ 12 AI / AO
– Analogue I/O data in
the word range
– with system diagnosis
AI = Analogue input
AO = Analogue output
Fig. 5.4
CC-Link memory mapping (≤ 12 analogue inputs and outputs)
Digital and analogue I/O modules (≤ 64 I/O and ≤ 8 AI / AO) with or without system diagnostics
– 4 stations
– Analogue I/O data in
the word range
– System diagnostics
(optional)
I = digital input
O = digital output
AI = Analogue input
AO = Analogue output
Fig. 5.5
CC-Link memory mapping (≤ 64 digital and ≤ 8 analogue inputs and outputs)
68
Bit range
RX
Inputs
Reserved
Station 1
Reserved
Reserved
Station 2
Reserved
Station 3
Reserved
Reserved
Reserved
Station 4
Remote Ready (RR = Bit 11)
Bit range
RX
Inputs
I15 ... I0
Station 1
I31 ... I16
I47 ... I32
Station 2
I63 ... I48
Station 3
Reserved
Reserved
Reserved
Station 4
Remote Ready (RR = Bit 11)
Word range
RY
RWr
Outputs
Inputs
Control
0 System diagnostics (16 I/O)
1 Reserved
Reserved
2 Reserved
3 Reserved
Control
0 AI 4
Reserved
1 AI5
2 AI6
3 AI7
Control
0 AI8
Reserved
1 AI9
2 AI10
3 AI11
Control
0 AI12
1 AI13
2 AI14
3 AI15
Word range
RY
RWr
Outputs
Inputs
O15 ... O0
0 System diagnostics (16 I/O)
1 Reserved
O31 ... O16
2 Reserved
3 Reserved
O47 ... O32
0 Reserved
O63 ... O48
1 Reserved
2 Reserved
3 Reserved
Control
0 AI0
Reserved
1 AI1
2 AI2
3 AI3
Control
0 AI 4
1 AI5
2 AI6
3 AI7
Festo – P.BE-CPX-FB23-24-EN – 1305a – English
RWw
Outputs
Reserved
Reserved
Reserved
AO4
AO5
AO6
AO7
AO8
AO9
AO10
AO11
AO12
AO13
AO14
AO15
RWw
Outputs
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
AO0
AO1
AO2
AO3
AO4
AO5
AO6
AO7

Advertisement

Table of Contents
loading

This manual is also suitable for:

Cpx-fb23Cpx-fb23-24

Table of Contents