Insulation Fault; Manual Shutdown - Ingeteam Ingecon Sun Power Series Installation Manual

Table of Contents

Advertisement

Installation manual

9.4.6. Insulation fault

Alarm 0400h is related to an insulation fault and can be one of two types:
External to the unit.
Internal to the unit.
External to the unit
To check whether the insulation fault is external to the unit, see
whether the Rpv+ and Rpv- impedances are displayed on the
display screen (selecting the fifth screen from the monitoring
menu). Given the insulation fault, one or both will be 0 or a low
figure.
Disconnect the power and open the DC breaker. If the Rpv+ and
Rpv- impedances cease to be invalid, the fault is in the photovol-
taic field. If one of them is balancing out and gives an interme-
diate reading, the inverter is triggering the insulation fault.
Inspect the installation.
Internal to the unit.
If the insulation fault is caused by the unit, you must cut the DC power
supply and wait 10 minutes before opening the inverter for the first time.
If the fault is not as specified earlier, it will be necessary to look for it in
the DC and/or AC part of the unit.
In the DC part of the unit, you will need to check the arresters and wiring.
Using a multimeter, check that the resistance and ground capacitance of
each pole of the DC battery bus is the same.
In the AC part of the inverter, check that the resistance of each of the inverter's outputs to ground are in the MΩ
range. Check also that the Q3 filter or the wiring of the unit's fans aren't producing the earth fault. To do so, open Q3
to separate circuits. In the filter is causing the ground fault you will need to check the wiring. If the fans are causing
the ground fault, you will need to disconnect terminals XVENT1.1 and XVENT1.2.

9.4.7. Manual shutdown

Code
Alarm
1000H
Manual shutdown
AAS2000IKI01
Reason for shutdown
Manual shutdown
Ingeteam Power Technology, S.A.
L1x
Q2x/Q3x
R1x
Switching harmonics filtering
J5
J6
Xventi.2
Xventi.1
Description
Manual shutdown with the emergency push
button via display or communications.
R2x
R3x
venti1
C1
63

Hide quick links: