Action Protocol For Responding To Incidents; Voltage And/Or Frequency Out Of Range - Ingeteam Ingecon Sun Power Series Installation Manual

Table of Contents

Advertisement

Ingeteam Power Technology, S.A.
Code
Overvoltages in the panel inputs.
This alarms indicates an out-of-range voltage at the PV input.
4000H
A voltage greater than 900 VDC will cause the equipment to shut down. Voltages greater than 1000 VDC
will damage the equipment.
Very low voltage on the input from the panels.
8000H
This alarms indicates an out-of-range voltage at the PV input.
The equipment will be on standby until the panel voltage reaches the necessary value for a connection.
Temperature alarm in the power electronics.
0020H
The temperature of the unit is too high and has stopped feeding current to the grid. When the tempera-
ture drops, the unit will reconnect.

9.4. Action protocol for responding to incidents

If the unit should stop interacting with the network due to the emergence of issues relating to the installation and/or
the inverter, the fastest way to resolve the issue is as follows:
1.
Check on the display the alarm and the reason for shutdown reported by the unit. Search in this guide's index
to see if the alarm or reason for shutdown is indicated. If it is covered, proceed to step 2; if on the contrary it is
not covered, take note of the unit's serial number and contact Ingeteam's telephonic technical service, the number
of which is listed on a sticker on the document pocket behind the door.
2.
Disconnect the unit from the supply. This will disconnect both the AC and auxiliary connections by opening
the thermomagnetic circuit breaker and the DC section by opening the PV array breaker. After AC and DC power
is switched off, wait 10 minutes before opening the unit, to ensure that their internal capacitance is discharged.
IMPORTANT
Only in the event of an insulation fault triggered by alarm 0400H will the AC power be switched off
and the DC power be left.
3.
Open the unit and find the section in this guide that deals with the alarm or reason for shutdown recorded
in the first step.
4.
Use a category III, 1000 V
proceed to carry out the checks listed here.
5.
If unable to solve the problem using this guide, take note of the unit's serial number and contact technical
service.
Below is a list of possible reasons for shutdown, their associated alarms and troubleshooting guidelines. If more than
one alarm takes place, the alarm on the display will be the sum of all active alarms.
E.g.:

9.4.1. Voltage and/or frequency out of range

One reason for shutdown associated with out-of-range voltage and/or frequency features the alarm codes listed below:
Code
Alarm
0001H
Grid frequency
0002H
Voltage
0003H
Grid frequency + voltage Grid frequency + voltage
In the event of a "0001H" and/or "0002H" alarm, you must check the status of the Q4 breaker protection and all the
58
Description
multimeter which can measure continuity, resistance and capacitance, and
DC
Code
Alarm
0001H
Grid frequency
0002H
Voltage
0003H
Grid frequency + voltage
Reason for shutdown
Grid frequency
Voltage
Description
Grid frequency out of range
Voltage out of range
Grid frequency out of range + Voltage out of
range
Installation manual
AAS2000IKI01

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents