Ingeteam Ingecon Sun Power Series Installation Manual page 36

Table of Contents

Advertisement

Ingeteam Power Technology, S.A.
Before any handling, check that there is no electrical hazard in the voltage input from the grid.
When checking that there is no voltage, wearing dielectric gloves and safety goggles approved for
electrical hazards is required.
Ingecon
Sun Power TL and Ingecon
®
Ingecon
Sun Power models with a transformer have four bimetallic terminal strips (three-phase plus neutral) for
®
connection to the electrical grid. The maximum allowable gauge for these terminal strips is 95 mm² in each phase.
Ingecon
Sun Power units with a transformer have the option of connecting all three phases or all three phases plus
®
neutral to the grid. If the three phases are connected, positions 2 and 3 of terminal strip X10 must be bridged with
a jumper. If the three phases plus neutral are connected, positions 1 and 2 of terminal strip X10 must be bridged
with a jumper.
Ingeteam recommends the connection of neutral in the case of Ingecon
Ingecon
Sun Power TL units have a plate for each of the three phases. This feed is shown in the figure on the left.
®
24
Sun Power with a transformer have different sorts of AC feed.
®
B
Units with a transformer
1
B
L1
L2
L3
Installation manual
2
3
N
Sun Power with a transformer.
®
AAS2000IKI01