GE PACSystems RX3i Command Line Interface Manual page 80

Profinet controller
Hide thumbs Also See for PACSystems RX3i:
Table of Contents

Advertisement

2
Field
SubModId
Leng
Value
RTA Timeout
RTA Retry
ConnReq
ConnRsp+
ConnRsp-
ConnDiff
ApRdyDif
DiscReq
DiscRsp+
DiscRsp-
DiscInd
AbortReq
AlmInd
DiagInd
ProcAlm
PullInd
PACSystems* RX3iPROFINET Controller Command Line Interface Manual – July 2011
2-64
The Submodule Identification value associated with the IO
Module. For GE Intelligent Platforms IO modules, the value is
the same as the ModId.
The length of data in bytes transmitted for the ObjType within the
RTC frame associated with the IOCR.
Actual data for the corresponding objType.
The timeout for acknowledging a RTA Data frame typically used
for signaling PROFINET alarms. RTATimeout =
RTATimeoutFactor × 100 ms. Valid values are 0x0001 to
0xFFFF. This field is set to a fixed value of 1.
The number of retries if an ACK is not received within an RTA
Timeout for an RTA Data frame. Valid values are 0x0003 to
0x000F. This field is set to 0x0003.
The number of Connect Requests sent to the PROFINET
Controller communications stack.
The number of Positive (successful) responses to Connect
Requests received from the PROFINET Controller
communications stack.
The number of Negative (failure) responses to Connect Requests
received from the PROFINET Controller communications stack.
The number of Connect Responses received from the
PROFINET Controller communications stack that include a
Module Diff Block.
The number of Application Ready indications received that
included a Module Diff Block.
The number of Disconnect Requests sent to the PROFINET
Controller communications stack.
The number of Positive (successful) responses to Disconnect
Requests received from the PROFINET controller
communications stack.
The number of Negative (failure) responses to Disconnect
Requests received from the PROFINET Controller
communications stack.
The number of Disconnect Indications received from the
PROFINET Controller communications stack.
The number of Abort Requests sent to the PROFINET Controller
communications stack.
Number of all Alarm indications received from the device.
Number of Diagnostic alarms received from the device. Includes:
Diagnosis and Diagnosis Disappears alarm types.
Number of Process alarms received from the device. Includes:
Process alarm type.
Number of Pull alarms received from the device. Includes: Pull
and Pull Module alarm types.
Description
show profinet
GFK-2572