GE PACSystems RX3i Command Line Interface Manual page 63

Profinet controller
Hide thumbs Also See for PACSystems RX3i:
Table of Contents

Advertisement

`
show node
Node Status Definitions
Field
Module
OK
Status
NOT OK
Config
Programmer
source
Other
Restart
Power Cycle
Reason
Reset Button
Command Line Interface
Fatal Error
Firmware Update
Go To Boot Firmware
Update
Over Temperature
Hardware Watchdog
Trip
Module Restart –
Unknown Reason
GFK-2572
Value
Module is operating correctly.
Module has encountered a fatal error.
All configuration items for the module were delivered via
the Programmer.
Some or all configuration items for the module were
delivered via means other than the Programmer. (e.g. via
Command Line Interface commands). Use "show config"
to see source for specific configuration items.
Power-cycle cause the last reset of the module.
A push of the reset button caused the last reset of the
module.
Execution of the Command Line Interface command
restart caused the last reset of the module.
A fatal error detected by the module caused the last reset
of the module.
An update for the module's firmware caused the last
reset of the module.
Start of firmware update caused the last reset of the
module.
Module detected an over temperature condition and
caused the last reset of the module.
Unexpected hardware watchdog expiration caused the
last reset of the module.
Cause of the last reset of the module is not known.
Chapter 2 Monitor Level Commands
Definition
2
2-47

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents