GE PACSystems RX3i Command Line Interface Manual page 75

Profinet controller
Hide thumbs Also See for PACSystems RX3i:
Table of Contents

Advertisement

`
show profinet
<<< IOCR 0x0001-(Output CR)-Update Period: 1 ms >>>
IOCRProperties:
MediaRedundancy:
RTClass:
IOCRTagHeader:
IOCR User Priority:
Vlan ID:
Current Data Status: 0x01
Station Problem Indicator: Problem detected
Provider State: Stop
Data Valid: Invalid
State: Backup
Len
FrmId SendClk(us) Ratio Phase FrmOffset WatchDg
----- ----- ----------- ----- ----- --------- -------
0040h ffffh
<<< API 0 >>>
ObjType
Slot#
-------
-----
OutIOCS
000h
OutIOCS
000h
OutIOCS
000h
OutIOCS
000h
OutIOCS
000h
OutIOPS
000h
OutData
000h
device-name>
Displaying Detailed Information about a Device's Alarm Status
The following example shows alarm status details for device number 1.
device-name> show profinet alarm 1
01-JAN-2000
00:06:38.0000
PNCDeviceName:
ProviderState:
Dev#
Vendor Device AR#
----
------ ------ ---
001
00B0h
0003h
<<< Alarm CR Status >>>
RTA Timeout: 100 ms
RTA Retry:
device-name>
GFK-2572
Screen Display
0x00000001
No media redundant frame transfer
RT Class 1
0xC000
6 (IO CR Priority)
0x000 (No VLAN)
1000.00
001
Subslot#
FrmOffset
--------
---------
0001h
0005h
0002h
0006h
8000h
0007h
8001h
0008h
8002h
0009h
0001h
0004h
0001h
0000h
Screen Display
device-name
Run
ARStat
------
001
LocCtrl
03
Chapter 2 Monitor Level Commands
0001h 00000000h
ModId
SubModId
---------
---------
00000001h
00000001h
00000001h
FFFF010Ah
00000001h
00100000h
00000001h
00010000h
00000001h
00020000h
00000001h
00000001h
00000001h
00000001h
DeviceName
-------
-------------------------------
remote-io-device1
DataHold APIs
-------- ----
0003h
0003h
001
Leng
Value
----
-------
0001
60h
0001
60h
0001
60h
0001
60h
0001
60h
0001
60h
0004
00h
2
2-59

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents