GE PACSystems RX3i Command Line Interface Manual page 77

Profinet controller
Hide thumbs Also See for PACSystems RX3i:
Table of Contents

Advertisement

`
show profinet
Field Definitions
The following table defines the fields shown in the preceding examples:
Field
PNCDevice Name
Provider State
Dev#
AR#
ARStat
DeviceName
Vendor
Device
Vendor Description
ARUUID
Redundancy Type
ARType
ARProperties
GFK-2572
The PROFINET Device Name of the PROFINET Controller.
The PROFINET Provider state that is sent with each RTC frame.
This reflects the state of the PLC CPU's Output Enable line. The
possible states and meaning are:
Run –the PLC CPU's Output Enable is enabled.
Stop –the PLC CPU's Output Enable Line is disabled.
The Device number associated with the Remote I/O Device.
A number the PROFINET Controller associates with the
Application Relationship's ARUUID that uniquely identifies a
particular AR. The possible values are 001 through 999.
Indicates the Application Relationship (AR) connection and
control status. The possible values are:
Disconn – the AR has not successfully been established with the
specified remote IO device.
LocCtrl – the AR is established and the local PNC has the
Primary AR.
RemCtrl – the AR is established and a different PNC has the
Primary AR.
NoCtrl – the AR is established but no PNC has the Primary AR.
Specifies the PROFINET Device Name of the associated Remote
IO Device.
Remote Device PROFINET Vendor ID used to specify an IO-
Device's vendor on the PROFINET network.
Remote Device PROFINET Device ID used to specify an IO-
Device's type on the PROFINET network.
An optional description provided by the Remote IO-Device that is
vendor specific (typically contains model name and/or catalog
number). If the IO-Device does not provide this information, the
field is blank.
A number that uniquely identifies a particular AR within the
system.
Indicates whether this AR is part of a PNIO System Redundancy
set or not. The possible values are Simplex AR and System
Redundancy AR.
Indicates the type of AR. The possible values are IOCARSingle
and IOCARSR. The IOCARSR indicates System Redundancy or
Configure in Run.
Displays the binary value of the AR Properties field for the
Application Relationship. The actual properties are decoded in
the indented fields just below the ARProperties field
(PullModuleAlarmAllowed, CompanionAR, etc.).