S120 Combi Power Modules
4.8 Electrical connection
4.8.4
Signal cables at the EP terminals
The shields of the signal cables connected to the EP terminals X21 and X22 are connected
using the shield clamp
connection involves the following steps:
● Secure the shield connection clamp on the S120 Combi. Use an SW3 wrench with 1.8
Nm tightening torque.
● Remove the insulation from the signal cables and crimp the individual cores with end
sleeves.
● Connect the cable cores to the EP terminals (screw terminals).
● Connect the cable shields as shown below.
Figure 4-27
118
①
from the accessories pack (Weidmüller: KLBÜ 4-13.5). The
Signal cables connected with the correct shield support
SINAMICS S120 Combi
Manual, (GH9), 07/2016, 6SL3097-4AV00-0BP5