Technical Data; Electrical Connection; Stripped Length For The Line Supply And Power Cables - Siemens SINAMICS S120 Combi Equipment Manual

Hide thumbs Also See for SINAMICS S120 Combi:
Table of Contents

Advertisement

S120 Combi Power Modules

4.8 Electrical connection

4.7.5.5

Technical data

Table 4- 19
Technical data of the external fan unit
6SL3161-0EP00-0AA0
Input voltage
Power consumption
Electronics current drawn at 24 V DC
Volumetric rate of air flow
Service life
Dimensions (W x H x D)
Weight
Degree of protection
4.8
Electrical connection
4.8.1

Stripped length for the line supply and power cables

Non-prefabricated MOTION-CONNECT power cables must be appropriately prepared before
being connected to the S120 Combi.
Note
Special issue for UL applications
For UL applications, use 60/75 °C copper wires/conductors.
Cables without connection cables for the motor holding brake
1. Cut the cable jacket to dimension A from the table below
2. Strip the single cores U, V, W and PE and crimp on end sleeves with insulation support
Cables with connection cables for the motor holding brake
1. Cut the cable jacket to 250
2. Cut the single cores U, V, W and PE to dimension A from the table below, strip and crimp
on end sleeves with insulation support
3. Strip the connection cables for the motor holding brake and screw to the brake connector
114
Unit
V
DC
W
A
m
/h
3
h
mm
kg
mm
± 5
Value
20.4 ... 28.8
18
0.8
290
50000 at 55 °C
258 x 104 x 86
1.5
IP54
SINAMICS S120 Combi
Manual, (GH9), 07/2016, 6SL3097-4AV00-0BP5