7.1.3.2

X1 line connection

Table 7- 1
X1 line connection
SINAMICS S120 Combi
Manual, (GH9), 07/2016, 6SL3097-4AV00-0BP5
Terminal
U1
V1
W1
PE connection
Technical data
Supply voltage:
3 AC 380 ... 480 V, 50 / 60 Hz
Type: Screw terminal 4 (Page 307)
Max. connectable cross-section: 4 mm
Tightening torque: 0.5 ... 0.6 Nm
Type: M5 screw at the housing
Tightening torque: 3 Nm
DC link components
7.1 Control Supply Module CSM
2