4.8.3

Power cables for motors

The motor power cables are connected at interfaces X2 to X5. The single cores of the cable
are labeled with U, V, W and PE. The cables are connected corresponding to the terminal
labels at the S120 Combi.
When using a power cable with connection cables for the motor holding brake, the cores for
the motor holding brake are connected at interface X11 (see the diagram below). In this
case, connect the cable shield of all cable cores. Fix the cable shield using the shield clamp.
When using a separate cable for the motor holding brake, its cable shield should be
connected to the associated shield support of the motor power cable.
Figure 4-26
NOTICE
Damage when strain relief is not used
The shield clamp does not provide strain relief. In the event that strain relief of the power
cable is not carried out separately using appropriate measures, the shield connection clamp
may be damaged.
• Install additional strain relief for the power cable.
SINAMICS S120 Combi
Manual, (GH9), 07/2016, 6SL3097-4AV00-0BP5
Shield connection clamp
Power cables with connection cables for the motor holding brake
Connector for the motor holding brake
Power cable connected at the S120 Combi
S120 Combi Power Modules
4.8 Electrical connection
117