Omron SYSMAC C2000H Operation Manual page 143

Hide thumbs Also See for SYSMAC C2000H:
Table of Contents

Advertisement

Data Movement
Description
Flags
Example
00003
00004
00004
00003
00003
00004
When the execution condition is OFF, BSET(71) is not executed. When the
execution condition is ON, BSET(71) copies the content of S to all words
from St through E.
S
3 4 5
2
BSET(71) can be used to change timer/counter PV. (This cannot be done
with MOV(21) or MVN(22).) BSET(71) can also be used to clear sections of a
data area, i.e., the DM area, to prepare for executing other instructions.
ER:
St and E are not in the same data area or St is greater than E.
Indirectly addressed DM word is non-existent. (Content of *DM word
is not BCD, or the DM area boundary has been exceeded.)
The following example shows how to use BSET(71) to change the PV of a
timer depending on the status of IR 00003 and IR 00004. When IR 00003 is
ON, TIM 010 will operate as a 50-second timer; when IR 00004 is ON, TIM
010 will operate as a 30-second timer.
@BSET(71)
#0500
TIM 010
TIM 010
@BSET(71)
#0300
TIM 010
TIM 010
TIM 010
#9999
St
3 4 5
2
St+1
3 4 5
2
St+2
3 4 5
2
E
3 4 5
2
Address Instruction
00000
LD
00001
AND NOT
00002
@BSET(71)
00003
LD
00004
AND NOT
00005
@BSET(71)
00006
LD
00007
OR
00008
TIM
Section 5-14
Operands
00003
00004
#
0500
TIM
010
TIM
010
00004
00003
#
0300
TIM
010
TIM
010
00003
00004
010
#
9999
137

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sysmac c1000h

Table of Contents