Data Movement
5-14-2
MOVE NOT – MVN(22)
Description
Precautions
Flags
5-14-3
BLOCK SET – BSET(71)
Limitations
136
Ladder Symbols
MVN(22)
@MVN(22)
S
D
When the execution condition is OFF, MVN(22) is not executed. When the
execution condition is ON, MVN(22) transfers the complement of the content
of S (specified word or four-digit hexadecimal constant) to D, i.e., for each
ON bit in S, the corresponding bit in D is turned OFF, and for each OFF bit in
S, the corresponding bit in D is turned ON.
Source word
TC numbers cannot be designated as D to change the PV of the timer or
counter. However, these can be easily changed using BSET(71).
Indirectly addressed DM word is non-existent. (Content of *DM word
ER:
is not BCD, or the DM area boundary has been exceeded.)
EQ:
ON when all zeros are transferred to D.
Ladder Symbols
BSET(71)
@BSET(71)
S
St
E
St must be less than or equal to E, and St and E must be in the same data
area.
Operand Data Areas
IR, SR, AR, DM, HR, TC, LR, #
S
D
Bit status
inverted.
Operand Data Areas
IR, SR, AR, DM, HR, TC, LR, #
S
IR, AR, DM, HR, TC, LR
St
E
IR, AR, DM, HR, TC, LR
Section 5-14
S: Source word
D: Destination word
IR, AR, DM, HR, LR
Destination word
S: Source data
St: Starting word
E: End Word