2.
Power Supply Cable Connection
Electric shock hazard
DANGER
Shut the power off before connecting the power supply cable.
Power Supply Cable Connection
Connect the power supply cable to the terminal on the backside of the unit.
Cable Specifications
For information on the tightening torque of the screws on the terminal block, refer to the following table.
Tightening Torque
Recommended Screwdriver
When Using Bare Cables
• Do not solder the end sections of power cable wires. Soldering may result in bad
CAUTION
• When using stranded wire for the power cable, make sure the strands are
Cable Size
Wire Length
When Using Ferrules
Recommended Ferrule (Pin type)*
Recommended Crimping Tool
* Select a ferrule according to the cross section area (diameter) of the power cable.
0.5 to 0.6 N•m (5 to 6 kgf•cm)
SZS 0.6 × 3.5 (Phoenix Contact)
electrical contacts.
sufficiently twisted.
Failure to do so may cause shorting between stray strands or adjacent electrodes.
Power supply cable: AWG 18 to AWG 14, twisted/single (1.0 to 1.6 mm diameter)
Frame ground (FG): AWG 20 to AWG 14, twisted/single (0.8 to 1.6 mm diameter)
6.5 mm
Phoenix Contact
Phoenix Contact
2. Power Supply Cable Connection
Power supply
Grounding
24 VDC ± 10 %
AI 0.75-6 GY
AI 1-6 RD
AI 1.5-6 BK
CRIMPFOX 6
3-3
3