Configuring/address space
4.2 Pulse width modulation PWM mode
4.2.1.9
High-speed output
The high-speed output function enables an output frequency of a maximum of 100 kHz with
an output current of a maximum of 100 mA. A high-speed output generates very steep
edges. The high-speed output generates signals at a higher frequency, but provides a lower
maximum load current.
The high-speed output is only available in two-channel operation and only without current
control.
The following table presents the minimum and maximum pulse duration, period duration and
frequency depending on whether or not the high-speed output is activated:
Pulse duration
Period duration
Frequency
48
Minimum value
High-speed output
High-speed output
deactivated
10 μs
100 μs
0,02 Hz
High-speed out-
activated
put deactivated
1,5 μs
85000000 μs (= 85 s)
10 μs
10 kHz
Technology Module TM Pulse 2x24V (6ES7138‑6DB00‑0BB1)
Manual, 05/2019, A5E35061186-AB
Maximum value
High-speed
output activated
100 kHz