Controlling The Output Channels Without Field Assignment - Siemens SIPLUS HCS4 00 Series Configuration

Heating control in tia portal
Table of Contents

Advertisement

8 Operating the Application
8.1 Operating the HCS4x00
8.1.4

Controlling the output channels without field assignment

Without the assignment of the channels to fields you can control each power output
channel of the POM individually, independent of the operating mode.
Table 8-5
No.
Action
Open the "LHcs4x00_WatchTablePut"
1.
watch table in the project tree.
2.
Set the
"LHcs4x00_Tags".control.heatingOn
bit for switching on the heating.
3.
The heating operation in the
"LHcs4x00_WatchTableGet" watch
table is displayed under the CIM
information.
4.
Control the power output channels in
the "LHcs4x00_WatchTablePut"
watch table via
"hcs[1].cyclicData.pom[1]" in DB
"LHcs4x00_Put" (value range 0 to
100%).
5.
Open the
"LHcs4x00_WatchTableGet" watch
table with the POM information.
The actual values of the controlled
power output channels of the POM
are displayed.
6.
Reset the
"LHcs4x00_Tags".control.heatingOn
bit again in the
"LHcs4x00_WatchTablePut" watch
table in order to switch the heating off.
HCS4x00Library
Entry ID: 109478117,
V2.2.1,
09/2018