On/Off Delay Mode; Function; Introduction; Output Sequence - Siemens ET 200SP Manual

Technology module tm pulse 2x24v
Hide thumbs Also See for ET 200SP:
Table of Contents

Advertisement

4.4

On/Off delay mode

4.4.1

Function

4.4.1.1

Introduction

In this operating mode, the respective channel of the technology module outputs pulses with
a specified switching delay relative to digital input DIn.0. You specify the On delay via the
control interface.
4.4.1.2

Output sequence

Starting the output sequence
In order to output the output sequence at the digital output DQn.A, the TM_CTRL_DQ control
bit (Page 126) must be set. To start the output sequence using the software enable, you set
the SW_ENABLE control bit (Page 89). The STS_SW_ENABLE feedback bit indicates that
the software enable in the technology module is active.
Technology Module TM Pulse 2x24V (6ES7138‑6DB00‑0BB1)
Manual, 05/2019, A5E35061186-AB
Configuring/address space
4.4 On/Off delay mode
79