4.3.1.6

Current measurement

The technology module measures the load current at the digital output. The measured value
of the current is returned as an S7 analog value in the MEASURED_CURRENT value in the
feedback interface (Page 76).
A valid measured value is available when the STS_ENABLE feedback bit is set after the first
period duration of the output sequence. The returned measured value is an average of the
measured values that were acquired over a time period of at least one period duration. If a
valid measured value is not available, the value 32767
Note
In order to use the current measurement, the high-speed output must be deactivated.
Measuring range and accuracy
The measuring range and accuracy are dependent on the channel configuration:
Two-channel opera-
tion
One-channel opera-
tion
(parallel connection)
May only be exceeded for a short time.
1
When this current value is exceeded, the ERR_DQA feedback bit will be set.
2
With constant period duration in the respective measuring period.
3
4.3.1.7

High-speed output

The high-speed output function enables an output frequency of a maximum of 100 kHz with
an output current of a maximum of 100 mA. A high-speed output generates very steep
edges. The high-speed output generates signals at a higher frequency, but provides a lower
maximum load current. The high-speed output is only available in two-channel operation.
The following table presents the minimum and maximum pulse duration, period duration and
frequency depending on whether or not the high-speed output is activated:
Pulse duration
Period duration
Frequency
Technology Module TM Pulse 2x24V (6ES7138‑6DB00‑0BB1)
Manual, 05/2019, A5E35061186-AB
Measured
Maximum measured
value
27648
32511
D
2 A
1
4 A
1
Minimum value
High-speed output
High-speed output
deactivated
10 μs
100 μs
0,02 Hz
is returned.
D
value
Period duration >
≙ ...
333 μs
D
2.37 A
±40 mA
2
4.74 A
±80 mA
2
High-speed out-
activated
put deactivated
1,5 μs
85000000 μs (= 85 s)
10 μs
10 kHz
Configuring/address space
4.3 Pulse train mode
Accuracy
3
Period duration <
333 μs
-40 mA ...
+100 mA
-80 mA ...
+200 mA
Maximum value
High-speed
output activated
100 kHz
67