The figure below shows one-channel operation in which you only configure Channel 0.
Figure 4-13
One-channel operation (parallel connection)
The following table presents the possible load current depending on whether or not the high-
speed output is activated:
Two-channel opera-
tion
One-channel mode
You configure the function in the hardware configuration using the "Channel configuration"
parameter.
Technology Module TM Pulse 2x24V (6ES7138‑6DB00‑0BB1)
Manual, 05/2019, A5E35061186-AB
Maximum output current
High-speed output deactivated
2 A
4 A
Configuring/address space
4.7 Parallel connection of channels
High-speed output activated
100 mA
Not permitted
125